In search for performance indicators of short-circuit current

interruption in vacuum

Citation for published version (APA):

Smeets, R. P. P., Lanen, van, E. P. A., Popov, M., & Sluis, van der, L. (2008). In search for performance

indicators of short-circuit current interruption in vacuum. In Discharges and Electrical Insulation in Vacuum, 2008 ISDEIV, 23rd International Symposium, 15-19 Sept. 2008, Bucharest, Romania (pp. 78-82). Institute of Electrical and Electronics Engineers. https://doi.org/10.1109/DEIV.2008.4676724

DOI:

10.1109/DEIV.2008.4676724

Document status and date: Published: 01/01/2008

Document Version:

Publisher’s PDF, also known as Version of Record (includes final page, issue and volume numbers)

Please check the document version of this publication:

• A submitted manuscript is the version of the article upon submission and before peer-review. There can be important differences between the submitted version and the official published version of record. People interested in the research are advised to contact the author for the final version of the publication, or visit the DOI to the publisher's website.

• The final author version and the galley proof are versions of the publication after peer review.

• The final published version features the final layout of the paper including the volume, issue and page numbers.

Link to publication

General rights

Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights. • Users may download and print one copy of any publication from the public portal for the purpose of private study or research. • You may not further distribute the material or use it for any profit-making activity or commercial gain

• You may freely distribute the URL identifying the publication in the public portal.

If the publication is distributed under the terms of Article 25fa of the Dutch Copyright Act, indicated by the “Taverne” license above, please follow below link for the End User Agreement:

www.tue.nl/taverne

Take down policy

If you believe that this document breaches copyright please contact us at: openaccess@tue.nl

(2)

In Search for Performance Indicators of

Short-Circuit Current Interruption

in Vacuum

R.P.P. Smeets

1

, E.P.A. van Lanen

2

, M. Popov

3

and L. van der Sluis

3

1KEMA T&D Testing, Utrechtseweg 310, 6812 AR Arnhem, the Netherlands 2University of Twente, P.O.Box 217, 7500 AE Enschede, the Netherlands 3Delft University of Technology, Mekelweg 4, 2628 CD Delft, the Netherlands

Abstract- Current interruption in vacuum is characterized

by a very rapid transition from an almost perfectly con-ducting arc plasma state to a very good insulating state. During the transition, the recovery process determines the success of the interruption.

The aim of this contribution is to derive characteristics from measurements of the initial ("current zero") stage of this recovery process, having the potential to indicate the quality of the interruption.

In the case of vacuum, a large number of measurements has been performed giving detailed information on the recovery process during the decay period of the post-arc plasma.

The best-known indicator is the post-arc current, drawn from the decaying residual plasma by the transient re-covery voltage. It turned out from measurement statistics, that post-arc current quantities (duration, peak value, charge) alone are not suitable as performance indicators. In addition, the role of conductivity (evolution) is exam-ined, also showing not a very strong relationship with performance.

It must be concluded that current-zero performance indicators for vacuum interruption are more difficult to define than for SF6 interruption. This suggests that vacuum interruption success is strongly related to di-electrical stesses, that are still relatively mild in the current zero period of a few microseconds duration.

I. INTRODUCTION

Current interuption in vacuum, as practically applied in vacuum circuit breakers, is strongly related - at least in the initial several microseconds - to the capability of the interrupter to change its conductivity from very large (in the arcing phase) to almost zero (in the isolating position) in a very short time. During this "recovery" period, a residual plasma (the post-arc plasma), remnant from the arc, should decay against the rapidly developing (circuit generated) transient recovery voltage (TRV) across the plasma, drawing the so-called post-arc current from the plasma.

Earlier research, combining current-zero measure-ments and modelling [1, 2, 3] has contributed to the un-derstanding of the post-zero processes of current inter-ruption in vacuum [4].

From R&D point of view, it would be desirable to derive characteristics (from measurements) of the initial stage of this recovery process having the potential to indicate the "quality" of the interruption. With such

indicator(s), the performance of the interrupter under the specific test conditions in terms of (arc) current and (re-covery) voltage should be quantified. Such performance indicators shall allow evaluation of tests not just in terms of "pass" or "not pass", but may quantify a margin (in a positive or a negative sense) from a certain critical value of the indicator.

Such an approach has been succesful in short-circuit current interruption in SF6 interrupters, generally applied at high voltage. In SF6, the measured arc con-ductivity 200 ns before current zero has been shown to be a very good predictor of interruption or failure [5, 6]. This result has triggered the authors to search for equally straightforward performance indicators in the case of vacuum interruption.

II CANDIDATE PERFORMANCE INDICATORS For industrially produced vacuum interrupters, meas-urable quantities during the interruption process are usually limited to current and voltage. During short-circuit tests, measurement systems having extreme resolution in magnitude and in time are nessesary [7], given the very low arc voltage (few tens of volt) before current zero and the small post-arc current (few am-pères) of very short (few microseconds) duration after interruption.

Moreover, just before current zero, there is a constant and low arc voltage and vacuum arc conductivity is high, up to the very moment of current interruption. This leads to the conclusion that there is no noticeable interaction with the external circuit before current zero. After current zero, post-arc current is normally a few to several ampères, and due to this, the period in which the circuit interacts with the (former) arc is limited to this time domain.

In the case of arcs in SF6, the situation is completely opposite, as the table below summarizes.

medium arc voltage before current zero

post-arc current after current zero few kVpk; changing 10 - 50 mA

SF6

arc-circuit interaction before current zero few tens Vdc; constant several A

vacuum

arc-circuit interaction after current zero XXIII-rd Int. Symp. on Discharges and Electrical Insulation in Vacuum – Bucharest - 2008

(3)

Fig. 3: Relationship beween peak-post arc current îpa and arc duration tarcin 50 Hz tests with current 25 - 35 kA. From this, it becomes clear that performance indicators

for vacuum, if any, have to be be sought in the time domain after current zero, whereas in SF6 this is the case before current zero.

A. Post-arc current

The post-arc current has been subject of investigation for many years, since it is one of the most distinctive electrical phenomena of short-circuit current inter-ruption with vacuum interrupters. Because the post-arc current shows a clear relation with the arcing con-ditions, it is reasonable to assume that it reflects the conditions inside the breaker immediately after current zero. This could provide researchers with a tool to investigate the interruption performance without having to open the interrupter to look inside. However, the post-arc current contains, unfortunately, a considerable scatter that masks a possible relationship between the arcing conditions and the post-arc current, see for ex-ample fig. 1, showing typical post-arc currents from two tests in succession with identical parameters.

This is probably due to the final position of the last cathode spots which, until now, can only be determined by inspection of the inside of the interrupter (see fig. 2).

Nevertheless, a relationship can be found between arcing stress and post-arc current. Plotting the peak value of post-arc current (îpa) as a function of arc

duration (from a test series with 50 Hz current 25 - 35 kA and rate-of-rise of recovery voltage (RRRV) 7.5 - 14 kV/μs), a significant increase of post-arc current can be identified for an arc duration > 7 ms, as expressed in fig. 3. It can be safely assumed that this indicates a sign-ificant increase of electrical stress, although no sign of failure to interrupt is observed yet.

In standard tests, the contribution at increased arc dur-ation to the post-arc current is two-fold: longer arc duration (higher thermal stresses to the electrodes) and increased contact distance (larger post-arc plasma vol-ume). Which of the two contributes most cannot be con-cluded easily from such tests.

It is even more challenging to find a relationship between post-arc current magnitude and interruption success/failure. Several cases are observed in which very large post-arc currents (up to many tens of ampères) are observed, without failure to interrupt. Fig. 4 shows some post-arc current traces, two of which ("late" and "extreme") are intuitively sign of approach-ing an interruption limit. This, however could not be confirmed by test-results: the current was interrupted even with exceptionally large post-arc current. The fact that - through interaction with the circuit - high post-zero conductivity results in mitigation of the transient recovery voltage (TRV) may be one of the decisive factors for this behaviour. Similar experiences were gained with vacuum generator breakers for very high current [8].

These post-arc current phenomena cannot be explained with the models published so far.

B. Post-zero conductivity

By quantifying the voltage across the post-arc plasma, Fig.1: Typical post-arc current traces obtained in two

tests under identical conditions

Fig. 2: At cathode spot extinction at position 1, more charge returns to the electrical circuit than in position 2

"normal" post arc current

"late" post arc current

"extreme" 60 A post arc current

time 5 us/div all trace current 1 A/div

Fig. 4: Three cases of post-arc current (25 kA in a 24 kV direct test-circuit) where inspite of late, long lasting and large post-arc current

(4)

Fig. 5: a) Post-arc current and b) post-arc conductivity of 3 different tests. Trace 1: RRRV = 15 kV/μs; trace 2: RRRV = 6 kV/μs; trace 3: RRRV = 4 kV/μs (all inherent values measured without arc)

Fig. 6: Post-arc plasma conductivity vs. arc duration at 0.5 μs after cz for 2 circuits: 6a (left): IEC 62271-100 L75 circuit (14 kA; 3.3 - 5.6 kV/μs)

6b (right): research circuit (25 - 35 kA; 7.5 - 14 kV/μs)

Fig.7: Relationship between post-arc conductivity 0.5 μs after cz G0.5 and post-arc charge Qpa (16 - 30 kA, 11 kV/μs) the (development of) conductivity can be evaluated.

This seems to be a more straightforward approach, be-cause conductivity, by definition, includes the arc-circuit interaction automatically.

Typical conductivity traces are shown in fig. 5 for three values of TRV rates-of-rise. Note the very rapid (the vertical scale is logarithmic) recovery. Here, the circuit does not influence the conductivity until approx. 1.5 μs after current zero, inspite of the widely varying current and voltages during this period.

A clear observation from fig. 5 is that the fastest recovery (in terms of conductivity) coincides with the steepest TRV and the highest post-arc current.

The next step is to consider the arc conductivity (G) at a certain instant after current zero, for example G0.5: the

conductivity 0.5 μs after current zero. There is a clear dependence of G0.5 on the arc duration, as demonstrated

by fig. 6, where two different circuits have been used. It can be recognised that the relationship between the con-ductivity-indicator G0.5 and stress (here arc duration) is

more evident than between post-arc current peak îpa and

arc duration (cf. fig. 3), although a varying current (fig. 6b) introduces a considerable scatter again.

C. Post-zero charge

The integrated post-arc current, Qpa = ∫ipa.dt, quantifies

the charge present in the intercontact gap. It has been

demonstrated that a clear relationship exists between post-arc charge and conductivity at a specific instant after current zero. If the interrupter's conductivity after current zero is small, little charge can transport through the gap, whereas the opposite is true for a high post-arc conductivity. As a result, the post-arc charge is pro-portional to the post-arc conductance. This is depicted in fig. 7. Although the results shown in this figure are from measurements with different arcing times, they show a distinctive trend.

Vapour particles are either generated directly by a cath-ode spot, or indirectly by vaporisation from the ancath-ode. If (after current zero), the amount of vapour is related to the amount of charge, then the post-arc charge Qpa

might be an indicator for the amount of vapour at cur-rent zero. However, it is impossible to calculate Qpa

when a reignition takes place during the post-arc current, since the determination of Qpa requires

the entire post-arc current.

Qpa relates rather linearly to G0.5 (see fig. 7),

and its coefficient changes only with the TRV values. In the first microsecond after current zero, the TRV is generally rather low, and pro-bably for this reason, the gap only occasionally re-ignites during this time. Therefore, it is always possible to measure G0.5 within the first

microsecond, and with a fixed coefficient, it is possible to determine Qpa, even if the gap

re-ignited during a post-arc current.

This leads to the idea of investigating G0.5 (as

an estimator proportional to vapour pressure) times contact distance (d) in order to find a critical value to discriminate between interruption and re-ignition. Such a reasoning would hold in the mechanism of vapour-induced Townsend-type break-down as an early failure mechanism in vacuum.

Fig. 8 shows G0.5d of 30 measurements from one test

series (current 25 - 35 kA, arc duration 1.5 - 9.6 ms and equal RRRV).

It shows a smooth transition from values of G0.5d for

which "early" re-ignition is rare to values for which "early" re-ignition occurs more frequently.

Beyond G0.5d ѩ 70 mm.Ω-1 (indicated in fig.7 with the

(5)

interruption

delayed reignition

early reignition

Fig. 8: Conductivity at 0.5 μs after cz (G0.5) times contact distance (d) of 30 measurements. The results are ordered in increasing values to facilitate

the search for a critical value

Attempts to relate the voltage at which re-ignition starts with G0.5d, in order to reconstruct in this way a

Paschen-type vapour related breakdown curve, were not succesful [3].

III RE-IGNITION

In vacuum, from current-zero analysis, the following types of re-ignition can be distinguished :

a. Immediate re-ignition (on the rising edge of post arc current) during the period that electrons are still present in the gap. The occurrence of this type is very rare, and has been observed exclusively when the rated current short-circuit current of the breaker is exceeded significantly [7]. This type of re-ignition is observed frequently in SF6 ("thermal" re-igition), and is the reason to verify its absence with the so-called "short-line fault" tests.

b. Early re-ignition (during the post-arc current period); this type of re-ignition occurs only rarely. This is also called sometimes a thermal re-ignition, initiated by post-arc current and initial TRV input of energy into the ex-arc plasma.

c. Delayed re-ignition (after decay of the post-arc cur-rent). In this case, re-ignitions occur under the influence of a TRV close to its peak value. The vast majority of re-ignitions fall into this category.

d. Late restrike (> half power frequency cycle after interruption). In switchgear standards, this failure is called "restrike" in stead of ignition. These re-strikes are commonly called "non-sustained disruptive discharge" (NSDD), and are inherent to vacuum switchgear. They seem to be independent from cur-rent zero phenomena.

IV CONCLUSIONS

Straightforward current-zero performance indicators for short-circuit current interruption can not be readily identified. It has been demonstrated that post-arc current on its own is not a suitable measure for interruption per-formance because a large post-arc current can mitigate initially the effect of transient recovery voltage.

The arc conductivity, as a measure for recovery seems to be a better candidate: multiplication of this con-ductivity (shortly after current zero) with current-zero contact distance has shown to have value in establishing a critical distinction between interruption and re-ignition.

A reason for not being able to identify near-zero in-dicators could be explained by the fact that re-ignition occurs (as observed) mostly after the post-arc period at relatively large values of the transient recovery voltage. This could imply that in vacuum - unlike the "thermal region" in SF6 - the current zero region is of less im-portance in the interruption process than the elevated TRV-related dielectrical stresses at a later time. The experience from testing, that well-designed vacuum interrupters normally show minor problems with steep values of TRV may support this assumption.

Hundreds of tests in direct as well as in synthetic test circuits, with transient recovery voltages rising far steeper than the standardised value for the short-line fault test-duty value in IEC 62271-100 suggest that typical "thermal re-ignitions", as known from SF6 circuit breakers are rare events in vacuum.

Further study should reveal whether this test-duty, newly introduced in the circuit breakers standards, is really relevant for vacuum switchgear.

REFERENCES

[1] E.P.A. van Lanen, M. Popov, L. van der Sluis, R.P.P. Smeets, "Vacuum Circuit Breaker Current-Zero Phenomena", IEEE Trans. on Plasma Science, vol. 33 no.5, pp. 1589-1593, Oct. 2005 [2] E.P.A. van Lanen, R.P.P. Smeets, M. Popov, L. van der Sluis,

"Vacuum Circuit Breaker Postarc Current Modelling Based on the Theory of Langmuir Probes", IEEE Trans. on Plasma Science, vol. 35 no.4, pp. 925-32, Aug. 2007

[3] P.G. Slade, "The Vacuum Interrupter, Theory, Design and Application", CRC Press 2008, ISBN 978-0-8493-9091-3 [4] E.P.A. van Lanen, "The Current Interruption Process in Vacuum",

Ph.D. Thesis, ISBN 978-90-5335-152-9, 2008

[5] R.P.P. Smeets, V. Kertész, "Evaluation of High-Voltage Circuit Breaker Performance with a New Validated Arc Model", IEE Proc. Generation, Transmission & Distribution, Vol. 147, No. 2, March 2000, pp. 121 - 125

[6] R.P.P. Smeets, V. Kertész, S. Nishiwaki, K.Suzuki, "Performance Evaluation of High-Voltage Circuit Breakers by Means of Current Zero Analysis", IEEE/PES T&D Conference Asia Pacific, Yokohama, Japan, 2002

[7] R.P.P Smeets, W.A. van der Linden, "Current-Zero Measurements of Vacuum Circuit Breakers Interrupting Short-Line Faults", IEEE Trans. on Plasma Science, vol.31 no. 5., pp. 852-858, Oct. 2003

[8] R.P.P. Smeets, J. Jäger, N. Anger, J.A.A.N. Hooijmans, "Test Ex-periences with a new Generator Circuit Breaker Based on Vacuum Technology", CIRED Conference, Session I, paper 0383, May 2007

Referenties

GERELATEERDE DOCUMENTEN

Nadat in Afzettingen van december 1999 werd aangekon- digd dat het afgelopen zou zijn met de bekende ontslui- ting in de Boven-Miocene Langenfeld Stufe besloot ik in. de loop van

Na mijn in funktie treding, 18 maart j .1., diende met betrekking tot de girorekening bij de Postbank en de bankrekening bij ABN/AMRO de wijziging van de beschikkings-.. bevoegdheid

die. tydperk, was daar geen uitbreiding van terrein nie buitekant die aangewese gebied wat reeds in die eerste jaar in gebruik was. Inteen- deel was daar 'n

paroisse d'Hatrival n' est autre que saint-Denis, patron primitif de St-Gilles- au-Pré, on peut conjecturer qu'il est également le fondateur de l'église St-Urs- mer

We show that the ion heat flux is weakened above the linear critical gradient by near- resonant energy transfer between the instability, the zonal flow, and a conjugate stable

Tabel 6B.. Percentages slachtoffers naar leeftijdk/asse. gccn cellen met mindcr dan 5 waamemingen). Er is sprake ccn hclangrijke afwijking wanJlecr:.. De toets is

The identified source of the vibrations that lead to the booming noise in the cabin was identified as the drive shaft assemblies, with the right side assembly contributing more than

Het graf was afgedekt door een laag die als oude cultuurlaag te interpreteren is en die bestond uit een vrij homogene okerkleurige zandleem met sporadisch een