• No results found

Comparison of Time-domain Measurement Techniques for Interference Analysis in Power Line Communication

N/A
N/A
Protected

Academic year: 2021

Share "Comparison of Time-domain Measurement Techniques for Interference Analysis in Power Line Communication"

Copied!
5
0
0

Bezig met laden.... (Bekijk nu de volledige tekst)

Hele tekst

(1)

978-1-7281-4796-3/19/$31.00 ©2019 IEEE

Comparison of Time-domain Measurement

Techniques for Interference Analysis in Power Line

Communication

Maarten Appelman1, Muhammad Ammar Wibisono1,2, Wervyan Shalannanda2, Niek Moonen1, Frank Leferink1,3 1University of Twente, Enschede, The Netherlands

2 School of Electrical Engineering and Informatics, Institut Teknologi Bandung, Indonesia 3Thales Nederland B.V., Hengelo, The Netherlands m.b.appelman@student.utwente.nl, m.a.wibisono@utwente.nl

Abstract— This paper presents the comparisons between time-domain voltage and current measurement techniques for interference analysis in Power Line Communication (PLC) application. Voltage measurement is performed by directly sensing the mains voltage from a speed-controlled water pump using a 1:1000 voltage divider, whilst the current is measured using three types of sensors: current clamp, hall element, and differential probe over a shunt resistor. Voltage and current from these sensors are read with a digital oscilloscope. Impedance and power are calculated as well using post-processing software, in which the results can be analyzed in the frequency domain using a spectrogram to observe the possibility of performing communication. Voltage and current transducers should have transfer functions which are independent of frequency when performing time-domain measurements.

Keywords—time domain, measurement, power line communication, phase shift, load, impedance.

I. INTRODUCTION

Interest in time-domain measurement in a mains network is increasing due to the time-dependent characteristics of the impedance of the loads in a power line [1]. Modern loads like Light Emitting Diode (LED) lamps, Switched-Mode Power Supplies (SMPS), speed-controlled water pumps, etc. are non-linear. These loads generate electromagnetic interference (EMI) in the power system, especially in the frequencies between 2 kHz to 150 kHz [2]-[3]. One of the victims of the EMI in the power system is the Power Line Communication (PLC), where it has been shown that a non-linear load such as Compact Fluorescent Lamps (CFL) can affect the performance of the communication [4]. To overcome these problems, a time-frequency diversity method has been proposed by [5] which shows that there are low-interference slots in the time domain which can be utilized for PLC. However, interference analysis in power line system requires analysis from the impedance of the grid as well. This calls for a technique for which the impedance of a certain load or even a complete network can be measured in the time domain and in real time.

One of the existing methods for measuring network impedances is performed by using spectrum analyzers, which can only measure the magnitude of the complex impedance in a grid [6]. Another measurement technique uses a Vector Network Analyzer (VNA) which can also measures the phase component of complex impedance [7]. However, a VNA is

not suitable for measurement below 10 kHz due to its low output power. The three-probe method proposed in [8] avoids the use of a VNA, as it used a signal generator in combination with a spectrum analyzer. The technique is, however still limited to frequency domain measurements. It relies on three current transformers with non-linear phase characteristics. This is not an issue for frequency domain measurements as these only require magnitude information. However, non-linear phase response of a sensor becomes an issue for time-domain measurements as the phase shift from the sensor can introduce an error to the impedance measurement. Time-domain impedance measurements require at least two probes with zero phase shift.

Time domain impedance and power measurements are required to identify the low interference area for communication purposes which for instance can be detected using cognitive radio or spectrum sensing. In order to reduce complexity of processing and thus reducing the stress of computational power, two probes with near zero degree phase shift is recommended as these are able to capture non-linear behavior of loads without any correction in either frequency or time domain.

Therefore in this paper, three different time-domain measurement techniques for measuring the voltage and current of a load connected to mains with minimum phase shift are researched. The measurements are performed by measuring the voltage and current from a speed-controlled water pump simultaneously as was shown in [9]. The voltage measurements are performed in the same way as in [10] by using a 1:1000 voltage divider which is connected to the mains power line, whilst the current measurements are performed by either using a current clamps, a hall-effect sensor [11] or a differential voltage probe over a shunt resistor. The voltage and the current from the sensors are measured simultaneously using a 2-channel digital oscilloscope. The three techniques are compared based on the time difference between the voltage and current peak, pulse width, rise time, fall time and the peak current. From the voltage and current measurements, the impedance and power consumption of the load can be obtained by using post-processing software [12]. The data can also be converted to the frequency domain and plotted in a spectrogram for the conventional frequency domain analysis as well.

(2)

This paper is structured in the following way: Section II describes the three different current measurement techniques and the possibility for real time determination of impedance and power, followed by the results in Section III and discussions in Section IV.

II. MEASUREMENT METHODS

For all three impedance measurement methods introduced in this paper, the voltage measurement is performed in the same way by directly sensing the 230V mains voltage using 1:1000 voltage dividers [10]. The current measurement is done by measuring the electromagnetic field around a conductor (indirect current sensing) or by measuring the voltage drop over a shunt impedance (direct current sensing), typically a resistor. Both of these methods give an output voltage relative to the input current. Direct current sensing relies on Ohm’s law, whilst indirect current sensing is usually dependent on both Ampere’s and Faraday’s law.

A. Current clamp

Current clamps utilize the law of induction and Ampere’s law in order to transduce the current 𝑖𝑖(𝑡𝑡), flowing through a conductor to a measurable voltage. This principle is best explained by (1), where 𝑣𝑣𝑖𝑖(𝑡𝑡) is the measured voltage from the current clamp, 𝑀𝑀 is the mutual inductance between probe coil in the current clamp and the current-carrying wire.

𝑣𝑣𝑖𝑖(𝑡𝑡) = −𝑀𝑀𝑑𝑑𝑑𝑑𝑑𝑑𝑖𝑖 (1)

This voltage needs to be integrated in order to find the measured current using (2).

𝑖𝑖(𝑡𝑡) = −𝑀𝑀1∫ 𝑣𝑣0∞ 𝑖𝑖(𝑡𝑡)𝑑𝑑𝑡𝑡 (2)

Integration can be achieved by both passive and active circuits. Passive circuits are mostly built inside the measuring coil and often utilizes the parasitic self-inductance of the coil in combination with a resistor, but the parasitic capacitance can also be used. Both techniques theoretically allow measurement in the extremely low frequency (ELF) range. Passive circuits can measure frequencies down to a few Hz. However, active circuits can measure frequencies below 1 Hz when implemented in magnetic core coils.

Active integration makes it possible to achieve linear integration and a sharp +90° phase shift at low frequencies, but introduces an upper frequency limit. Active integration current sensing systems are especially attractive for measuring coils with low self-inductance like the Rogowski coil. The self-inductance of the coil causes non-linear frequency responses, which only gets worse as the inductance increases.

Integration can also be done numerically. This is nowadays a standard procedure but has the disadvantage that signal processing is needed before analysis, and it results in higher sensitivities for higher frequencies. When the sample rate is large enough, the trapezoidal rule can be used to obtain

the signal’s integral and maintain a measurement uncertainty below 1%.

B. Hall-element sensor

Hall-element sensors utilizes Hall-effect where the Lorentz force causes electrical charges to move when they are exposed to a magnetic field. A voltage relative to the magnetic field occurs due to this effect when a thin conducting sheet is placed perpendicular to a magnetic field while a control current is running through the sheet as shown in Fig. 1. This voltage is given by (3),

𝑉𝑉𝐻𝐻= 𝐼𝐼𝐶𝐶∙ 𝐵𝐵 ∙ 𝐾𝐾𝑑𝑑 (3) where 𝑉𝑉𝐻𝐻 is the measured Hall voltage, 𝐼𝐼𝐶𝐶 is the control current, 𝐵𝐵 is the magnetic flux density, 𝐾𝐾 is the Hall constant and 𝑑𝑑 is the thickness of the sheet [11].

Fig. 1. Hall-effect sensor

C. Differential probe

A straightforward technique to measure the current is to implement a shunt resistor and measure the voltage across the resistor. The current can then be calculated by applying Ohm’s law. This voltage should be measured with a differential probe in order to have an accurate measurement that is not interfered by the common mode (CM) load voltage. Therefore, a high Common Mode Rejection Ratio (CMRR) is needed to keep the CM voltage from disturbing the measurements when 𝑅𝑅𝑠𝑠ℎ𝑢𝑢𝑢𝑢𝑑𝑑<< 𝑅𝑅𝑙𝑙𝑙𝑙𝑙𝑙𝑑𝑑. This is achieved by either introducing a galvanic isolation or by using very high impedance resistors. Using a transformer would be disadvantageous as this will introduce phase shifts, but optical isolation or a high ohmic resistive input impedance should prevent this problem. However, there is a tradeoff between these two solutions. Whilst the galvanic isolation gives a higher CMRR, it lowers the dynamic range.

1. D. Impedance and Power Measurement

The three current measurement methods introduced in this paper have the potential to accurately measure the mains current in the time-domain between 2 kHz to 150 kHz bandwidth. They can be implemented in so-called breakout-boxes in combination with the 1:1000 voltage dividers. If a load is connected to this breakout-box, the output voltage 𝑣𝑣(𝑡𝑡) and current 𝑖𝑖(𝑡𝑡) can be used to find the instantaneous

(3)

impedance 𝑍𝑍(𝑡𝑡) and power 𝑃𝑃(𝑡𝑡) using (4) and (5), respectively

𝑍𝑍(𝑡𝑡) =𝑣𝑣(𝑑𝑑)𝑖𝑖(𝑑𝑑) (4) 𝑃𝑃(𝑡𝑡) = 𝑣𝑣(𝑡𝑡) 𝑖𝑖(𝑡𝑡) (5)

III. MEASUREMENT SETUP AND RESULTS

The measurements were performed using a speed-controlled water pump as the load. It is a non-linear load which produces very steep pulsed currents. The current is measured using three types of current sensors: the TA189 current clamp, HO-150-NSM hall-effect sensor and the TA043 differential probe. The three techniques are compared based on the time difference between the voltage and current peak (∆𝑡𝑡𝑝𝑝𝑝𝑝𝑙𝑙𝑝𝑝𝑠𝑠), pulse width (τ ), rise time (𝑡𝑡𝑟𝑟𝑖𝑖𝑠𝑠𝑝𝑝), fall time (𝑡𝑡𝑓𝑓𝑙𝑙𝑙𝑙𝑙𝑙 ) and the peak current (𝐼𝐼𝑝𝑝𝑝𝑝𝑙𝑙𝑝𝑝). The voltage and the current are then plotted by the Picoscope 4262. The measurement setup is shown in Fig. 2.

Fig. 2. Schematic of the measurement setup

A. Current clamp

The voltage and current sensor used in this measurement is similar to the one in [9]. The current sensor in Fig. 3 has wires for measuring line, earth and neutral current 𝐼𝐼𝐿𝐿, 𝐼𝐼𝐸𝐸 and 𝐼𝐼𝑁𝑁, respectively, which are extended exterior to the breakout-box, allowing the current clamp to be placed around it.

Fig. 3. Schematic of the current clamp breakout-box The TA189 has a 100 kHz bandwidth and a 30 A measuring range. The measurement results in Fig. 4 show that there is 1.12 ms time difference between the peak value of the voltage and current. The pulse width of the current is 2.4 ms with a rise time of 0.24 ms and a fall time of 1.64 ms. The current peak is measured at 3.62 A.

Fig. 4. Measured voltage (blue) and current (red) from water pump using TA189 current clamp

B. Hall-effect sensor

The breakout-box in Fig. 5 uses two HO-150-NSM hall-effect sensors with current range of 150 A. The measurement results are very noisy as can be seen in Fig. 6. However, these sensors are still suitable for educational purposes as it is able to show the voltage and current waveforms without any calibration or post-processing. In case of monitoring the mains voltage and current with low frequency transients, this probe can still be used. Hall-effect sensors also do not require additional probes or auxiliary equipment other than an oscilloscope and a 5 V DC power supply.

Fig. 5. Schematic of the Hall-effect sensor breakout-box

Fig. 6. Measured voltage (blue) and current (red) from water pump using HO-150-NSM Hall-effect sensor

(4)

Fig. 6 shows that there is a 1.16 ms time difference between the peak value of the voltage and current. The pulse width of the current is 2.24 ms with rise time of 0.65 ms and fall time of 1.6 ms. It shows a current peak of 4.7 A.

C. Differential probe

Unlike the previous sensors, the accuracy of the differential probe sensor is not only dependent on the probe, but also on the shunt resistors. The shunt resistors in the sensor have a flat frequency response between DC and 1 MHz. The TA043 differential voltage probe was used for these measurements. The measurement results in Fig. 8 show noise at low currents. Making this method unsuitable for measuring small currents.

Fig. 7. Schematic of the differential probe breakout-box

The measurement results shown in Fig. 8 shows a 0.95 ms time difference between the peak value of the voltage and current. The pulse width of the current is 2.56 ms with rise time of 0.26 ms and a fall time of 1.6 ms and a peak current of 4.14 A.

Fig. 8. Measured voltage (blue) and current (red) from water pump with TA043 differential probe

IV. DISCUSSIONS

The current pulse characteristics from the three measurements are summarized in Table 1. The three techniques investigated in this paper give similar time difference between the voltage and current peak (∆𝑡𝑡𝑝𝑝𝑝𝑝𝑙𝑙𝑝𝑝𝑠𝑠),

pulse width (τ ) and fall time (𝑡𝑡𝑓𝑓𝑙𝑙𝑙𝑙𝑙𝑙). The results from TA189 shows the least amount of distortion, while the output of the HO-150-NSM Hall-effect sensor is very noisy, which is influence can be seen in the significant difference in the rise time (𝑡𝑡𝑟𝑟𝑖𝑖𝑠𝑠𝑝𝑝) and the peak current (𝐼𝐼𝑝𝑝𝑝𝑝𝑙𝑙𝑝𝑝). This significant difference is possibly caused by the limited dynamic range of the Hall-effect sensor. A low-pass filter could be implemented either digitally or physically in order to reduce the high frequency noise.

TABLE I. MEASURED PULSE CHARACTERISTICS Parameters TA189

HO-150-NSM TA043 ∆𝑡𝑡𝑝𝑝𝑝𝑝𝑙𝑙𝑝𝑝𝑠𝑠 (ms) 1.12 1.16 0.95 τ (ms) 2.4 2.24 2.56 𝑡𝑡𝑟𝑟𝑖𝑖𝑠𝑠𝑝𝑝 (ms) 0.24 0.65 0.26 𝑡𝑡𝑓𝑓𝑙𝑙𝑙𝑙𝑙𝑙 (ms) 1.64 1.6 1.6 𝐼𝐼𝑝𝑝𝑝𝑝𝑙𝑙𝑝𝑝 (A) 3.62 4.7 4.14

Based on Table 1, it can be seen that TA189 gives the best results due to the low distortions and noise. From the measurement result of TA189, the impedance and the power from the speed-controlled water pump are calculated using post-processing software [12] and plotted against time as shown in Fig. 9.

Fig. 9. Measured impedance (blue) and power (red) from water pump using TA189 current clamp

From the impedance measurement results (blue), it can be seen that there are negative impedance pulses. This could be caused by the inaccuracy of the current clamp when measuring low currents. In the power measurement results (red), negative power can be observed as well. This issue has to be solved in future work in order to obtain correct impedance and power measurement, as impedance and power measurement is also important for interference analysis in a power line communication system. A spectrogram is plotted in Fig. 10 to observe the possibility of PLC. The spectrogram shows the interference power against time and frequency

(5)

during one cycle of the mains voltage (20 ms). It can be seen that the interference repeats every half of the mains voltage cycle (10 ms) with dominant frequencies between DC and 50Hz. There are also higher frequency interferences as well, especially between 60 kHz and 70 kHz which are caused by the distorted mains voltage signal. From the spectrogram, the slots for communication with a relatively low interference level (-60 dB/Hz) are shown in red boxes.

Fig. 10. Spectrogram of the measured power from TA189 current clamp sensor

V. CONCLUSIONS AND FUTURE WORKS

The comparison of three time-domain measurement techniques for interference analysis in power line communication applications have been presented. The TA189 current clamp has the lowest noise and distortion compared to the other sensors. However, the negative impedance pulses shows that improvements have to be made to the time-domain impedance measurement using this sensor. Nevertheless, the power measurement shows a better result which can be used for interference analysis in PLC application using a spectrogram.

ACKNLOWLEDGEMENT

This research is a part of SCENT (Smart City EMC Network for Training) project and COST (European Cooperation in Science and Technology) which are funded by the European Union’s Horizon 2020 research and innovation program. The results found reflect the author’s view only.

REFERENCES

[1] B. J. A. M. van Leersum, R. B. Timens, F. J. K. Buesink and F. B. J. Leferink, "Time domain methods for the analysis of conducted interference on the power supply network of complex installations," 2014 International Symposium on Electromagnetic Compatibility, Gothenburg, 2014, pp. 605-610.

[2] Frank Leferink, “Conducted Interference, Challenges and Interference Cases”, IEEE Electromagnetic Compatibility Magazine, Vol. 4, Issue 1, 2015, Pages 78-85.

[3] CENELEC TR 50627, Study Report on Electromagnetic Interference between Electrical Equipment/Systems in the Frequency Range Below 150kHz, November 2015

[4] A. Emleh, A. S. de Beer, H. C. Ferreira and A. J. H. Vinck, "The impact of the CFL lamps on the power-line communications channel,"

2013 IEEE 17th International Symposium on Power Line Communications and Its Applications, Johannesburg, 2013, pp.

225-229.

[5] I. Setiawan, C. Keyer, F. Buesink and F. Leferink, "Time-frequency diversity for solving e deadlock in defining interference levels in power lines," 2016 International Symposium on Electromagnetic Compatibility - EMC EUROPE, Wroclaw, 2016, pp. 364-369. [6] K. Y. See and J. Deng, "Measurement of noise source impedance of

SMPS using a two probes approach," in IEEE Transactions on Power Electronics, vol. 19, no. 3, pp. 862-868, May 2004.

[7] V. Tarateeraseth, B. Hu, K. Y. See and F. G. Canavero, "Accurate Extraction of Noise Source Impedance of an SMPS Under Operating Conditions," in IEEE Transactions on Power Electronics, vol. 25, no. 1, pp. 111-117, Jan. 2010.

[8] J. Tan, D. Zhao and B. Ferreira, "A method for in-situ measurement of grid impedance and load impedance at 2 k–150 kHz," 2015 9th International Conference on Power Electronics and ECCE Asia (ICPE-ECCE Asia), Seoul, 2015, pp. 443-448.

[9] B. ten Have, T. Hartman, N. Moonen, C. Keyer ,F. Leferink, "Faulty Readings of Static Energy Meters Caused by Conducted Electromagnetic Interference from a Water Pump", International Conference on Renewable Energies and Power Quality, Tenerife, 2018.

[10] C. Keyer, F. Buesink and F. Leferink, "Mains Power Synchronous Conducted Noise Measurement in the 2 to 150kHz band," in EMC EUROPE , Wroclow, 2016.

[11] LEM Application Notes: Isolated current and voltage transducers. Characteristics–Applications–Calculations. 3rd ed., Geneva, Switzerland: LEM Coporate Communications, 2010.

[12] T. Hartman, N. Moonen and F. Leferink, "Direct Sampling in Multi-channel Synchronous TDEMI Measurements," 2018 IEEE 4th Global

Electromagnetic Compatibility Conference (GEMCCON),

Referenties

GERELATEERDE DOCUMENTEN

De vergelijking van de koppelkromme kan nu op de volgende wijze worden afgeleid. De oorsprong van een rechtsdraaiend, rechthoekig assenstelsel wordt in het gestelpunt Ao

Vóór de aanleg van het Merovingisch grafveld moet er op dezelfde plaats ook een Romeins grafveld geweest zijn.. Op de vrijgebleven ruimten tussen de Merovingische bijzettingen

Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of

Aangezien alle aangesneden sporen tijdens het vooronderzoek onderzocht konden worden, en geen indicaties werden aangetroffen voor bijkomende archeologische sporen of

onmisbaar hulpmiddel bij de inter- pretatie van meetresultaten en het levert aanwijzingen voor de opzet van verdere experimenten die moe- ten leiden tot verfijning en

Different broadening mechanisms of resonance lines are considered (Doppler, Stark, Resonance, and Vander Waals broadening). The Vander Waals broadening is

4 Department of Obstetrics and Gynaecology, University Hospitals, Leuven, Belgium, 5 OB/Gyn, University Hospitals, Leuven, Belgium, Early Pregnancy and Gynaecology Ultrasound Unit,

Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of