\\ndis.be\dfsroot09\OPR\KCE_AFDELING\PROJECTEN\2 ONTWERP\E-plan\Concepten\Decentrle Productie Projektdirectory: 14/02/2022 Plotdatum:

No.

Vrg bl.

Wijziging

+.00/1

0 1

Datum Naam

2 3

Decentrale Productie >= 1MVA met telecontrolekast versie 4

4 5

Ingeluste Klantcabine

6

Tek. nr:

Tekenaar:

Datum:

7

31/01/2019

Ingeluste Klantcabine QJZ868

8

Hoogste pag.

Groep Plaats

1

= +

Principeschema V1 Rev.01

9

Bl.

Vlg bl. =MS+4/1

1

14/02/2022 15:26:16

Principeschema

=MS+1 Aankomstcel

Wega x2 C

Fluvius 1 (Line In)

=MS+2 Vertrekcel

Wega x2 C

Fluvius 1 (Line Out)

Korstsluitverklikker Horstmann Compass A

Back-Up Disconnect Switch

Disconnect Switch

~

Korstsluitverklikker Horstmann Compass A

TI TI TI TI

TP

TI TP

TI TP

TI TP

=MS+3 Algemene Beveiliging

=MS+4 Meetcel

=MS+5 =MS+6

Vertrekcel

=MS+7 Vertrekcel

=MS+8 Vertrekcel

Analog/Digital Signals

OR

Synchro Check TI

TP

Production Unit 1

TI

TI

For each Production Unit 25S30 25S60

25S60 Only in case of offtake

power >= 300kVA 25S30

Middenspanningsinstallatie =MS

-FCI -FCI

=PU1 +MS

Production Unit 1 Middenspanningscel

By Customer

01 Compass B wordt Compass A 14/02/2022 D.A.

-QAB2 -QAB1

=TCK +1 versie 4.0

Télécontrolekast

RS-485

-X102 -KFR1

DSO RTU

230VAC By Customer

-Voeding 230VAC

=SMV +1

1

2

-FCZ

=TEL +1

-X1

+.00/1.7 TVS

TP

=FLEX +1

1

-Q2

2 +.00/1.9 1

-Q1

2 1

-Q1

2

-Voeding 230VAC:by Customer TI

RS-485

-X103

RS-485

RJ45

-X100

RJ45

-X104

DER -RTU

-X101

RJ45

-X104 -DER SI

Safety Interface

By Customer

-X100

-X100

By Customer

-X101

-P1

Socomec Diris B-30

-22.1

+.00/1.7 Landis & Gyr

I 01 I 02 I 03 I 04

black

Yellow

red

=SMV +2

1

2

-FCZ

=TEL +2

AMR Production Unit 1

-X1

+.00/1.7 TVS

TP

=FLEX +2

Measuring Device Production Unit 1

1

-Q2

2 1

-Q1

2 1

-Q1

2

-Voeding 230VAC:by Customer TI

RS-485

-P1

Socomec Diris B-30

-22.1

+.00/1.7 Landis & Gyr

I 01 I 02 I 03 I 04

black

Yellow

red

RS-485

=FLEX+...

=PU1 +SB

Productie Unit 1 Stuurbord

-FZF1

Netontkoppelbeveiliging

NOB

-FCA1

-FCA1

-WGSTCK1/1

Interface B3.3 3G1.5 LIYCY-JZ

-WGSTCK1/2

RS 485 Measuring Device 3G1.5 LIYCY-JZ

-WGSMS2/1

Interface B3.3 3G1.5 LIYCY-JZ

-WGSMS4/3

TP Netontkoppelbeveiliging 4x...

LIYY

-WGSTCK1/3

Interface B3.1 10G1.5 LIYCY-JZ

-WGSPU1SB/1

230VAC by customer 3G2.5 XVB

-WGSTCK1/4

Interface B1.1 Analog 16G1.5 LIYCY-JZ

-WGSPU1MS/2

TP AMR Production Unit 1 4x...

LIYY

-WGSSMV2/2

TP Measering Device Production Unit 1

4x...

LIYY

-WGSPU1MS/1

TI AMR Production Unit 1 6x...

LIYY

-WGSTEL2/1

230VAC Measuring Device Production Unit 1 3G1.5 XVB

-WGSSMV2/3

TP AMR Production Unit 1 4x...

losse bedrading

-WGSMS4/2

TP AMR Grid Connection Point 4x...

LIYY

-WGSSMV1/2

TP Measering Device Grid Connection Point 4x...

LIYY

-WGSMS4/1

TI AMR Grid Connection Point 6x...

LIYY

-WGSTEL1/1

230VAC Measuring Device Grid Connection Point 3G1.5 XVB

-WGSSMV1/3

TP AMR Grid Connection Point 4x...

LIYY

-WGSVB1/1

230VAC AMR Grid Connection Point 3G1.5 XVB

-WGSFLEX1/1

RS485 Measuring Device 3G1.5 LIYCY-JZ

-WGSVB2/1

230VAC AMR Production Unit 1 3G1.5 XVB Interface B1.1 Digital

min. S/FTB Cat 6.

-WGCTCK1/5

IEC60870-104 Protocol +.00/1.0

+.00/1.0

+.00/1.1

+.00/1.6

+.00/1.6

+.00/1.6

+.00/1.8

+.00/1.1

+.00/1.3 +.00/1.2

+.00/1.8

-RJ12 5A Adapter

+.00/1.6

+.00/1.6

+.00/1.6 +.00/1.8

+.00/1.8

-RJ12 5A Adapter

+.00/1.9 +.00/1.7

+.00/1.7 +.00/1.2

+.00/1.7 +.00/1.4

+.00/1.4 +.00/1.4

+.00/1.4

+.00/1.5

+.00/1.4

+.00/1.7

Referenties

GERELATEERDE DOCUMENTEN

Voordat een lokale productie-installatie door Fluvius in dienst kan genomen worden, moet voor deze installatie onder meer een keuringsverslag conformiteit A.R.E.I..

Forfaitaire prijzen voor exploitatie van intraparkinstallaties, geldig in 2022 Deze tarieven zijn contractueel indexeerbaar.. 1.1 Hoogspanningskabels In deze prijs

De netgebruiker heeft het recht deze pulsen ter beschikking te stellen aan de leverancier en of toegangsverantwoordelijke van zijn keuze, dit met de beperking dat wij als DNB

Bedrijfsregime: continu parallel met het distributienet :ja/nee eilandwerking voorzien : ja/nee. netto-injectie in het distributienet

klassieke synchrone machine klassieke assynchrone machine machine met vermogenelectronica (soft start inventoren). merk: <

[r]

Afstanden ‘A’ en ‘B’ variëren naargelang de afmetingen van de gasmeetinstallatie, welke op zijn beurt afhankelijk is van het gevraagde debiet/vermogen.. Inlaat van de cabine

naargelang de afmetingen van de GMI, welke op zijn beurt afhankelijk is van het gevraagde debiet/vermogen. Afstand ‘X’ van het