Concentration versus m3 air per hour
Citation for published version (APA):Loomans, M. G. L. C. (2017). Concentration versus m3 air per hour: the battle of the assessors? In AIVC 2017 Workshop on IAQ metrics: Is ventilation the answer to indoor air quality control in Buildings? Do we need performance-based approaches?, 14-15 March 2017, Brussels, Belgium
Document status and date: Published: 14/03/2017 Document Version:
Accepted manuscript including changes made at the peer-review stage Please check the document version of this publication:
• A submitted manuscript is the version of the article upon submission and before peer-review. There can be important differences between the submitted version and the official published version of record. People interested in the research are advised to contact the author for the final version of the publication, or visit the DOI to the publisher's website.
• The final author version and the galley proof are versions of the publication after peer review.
• The final published version features the final layout of the paper including the volume, issue and page numbers.
Link to publication
General rights
Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights. • Users may download and print one copy of any publication from the public portal for the purpose of private study or research. • You may not further distribute the material or use it for any profit-making activity or commercial gain
• You may freely distribute the URL identifying the publication in the public portal.
If the publication is distributed under the terms of Article 25fa of the Dutch Copyright Act, indicated by the “Taverne” license above, please follow below link for the End User Agreement:
www.tue.nl/taverne
Take down policy
If you believe that this document breaches copyright please contact us at:
openaccess@tue.nl
providing details and we will investigate your claim.
CONCENTRATION VERSUS M
3AIR PER HOUR –
THE BATTLE OF THE ASSESSORS?
Marcel Loomans
Eindhoven University of Technology P.O. Box 513; VRT 6.23 Eindhoven, The Netherlands
*M.G.L.C.Loomans@tue.nl
KEYWORDS
Ventilation effectiveness, air quality, performance, prescriptive, integral design
1 ABSTRACT
The opposite of the performance approach is the prescriptive approach. If we refer to an amount of air changes per hour (ACH) or a flow rate in m3 air per hour (qv) we assume a certain performance of the ventilation as with these parameters we now prescribe the
ventilation. But, with focus on the indoor environment, a certain ‘x’ m3 air per hour is not the targeted outcome of ventilation. What is desired of ventilation are performances such as health and (local) comfort; for example the sleep quality in a sleeping room. Instead of air change per hour we should be talking about air quality and thermal comfort or maybe even physiological indicators that directly relate to health and comfort.
While a link with physiological indicators may yet be a bridge too far in most cases, the advantage of a prescribed ACH or qv is clear. It is much simpler to assess. But the assessment is at system level, not at room level! The latter is much more complex and is an integrated outcome. ACH or qv may not be sufficient if we look for example at the ventilation efficiency of different diffusers in a living room (Figure 1 [left]). Another example, in this case for school ventilation with underfloor air distribution, may see a transition from displacement to mixing ventilation if the air flow rate is increased (ref. Archimedes number; Figure 1 [right]). For the latter, guideline requirements on qv (> 90 m3/h per supply grille) would result in a less efficient mixing situation.
Axial diffuser
Radial diffuser
Figure 1: Local air change index in a living room with the same air flow rate but different diffusers (higher value is better; ±100% is mixing) [left]; air change efficiency (ACE) as function of the air supply rate [right].
As another example, available design guidelines (rules of thumb) for cleanrooms are not optimized to actual operation. Focussing on the air quality, apart from local contaminant removal efficiency, detailed knowledge about sources and use time could easily reduce fan energy use in clean rooms by about 60%. Adherence to the required air quality (ISO class) when in use would still be ensured. The prescribed approach therefore limits optimization possibilities and indoor species pollutant concentration is a better performance indicator. Another example refers to operating theatre ventilation. Prescribed unidirectional flow systems with a set supply velocity have been the standard in the Netherlands. New guidelines focus on air quality performance requirements at the wound area (particle concentration). This can result in a design solution where approximately only 10% of the earlier prescribed air flow rate is required to arrive at the same air quality level (Figure 2). An additional advantage in this case stems from optimizing the room climate system to, e.g., comfort purposes.
Figure 2: Local ventilation solution at wound area and instrument table [left]; CFD assessment of the relative particle concentration (0% is optimal) [right].
So, several examples show that ACH and qv do not provide the answer to an optimally performing ventilation system in a design. Functional requirements and related performance indicators are required to come to a suitable, integrated design solution. However, when these design solutions are tested according to specific use scenarios, and sensitivity and uncertainty are identified and quantified, it is possible to refer back to ACH and qv as performance
indicators for testing the performance in practice. They now however represent more than just the system performance; they represent a design parameter for the optimal functioning at room level.
However, buildings and their designs are unique, certainly in combination with their usage. Therefore, it will not be easy to assure that the ventilation performance is assessed in detail before reference can again be made to ACH and qv. Usually they will still indicate system performance. It is the complexity of assessing the ventilation effectiveness that will keep the battle between concentration versus ACH/qvalive for some years to come.
2 ACKNOWLEDGEMENTS
The work summarized above and in the presentation builds on work performed in cooperation with several Master and Graduate students. Their contributions are gratefully acknowledged. The co-supervision of these students by prof.dr.ir. Jan Hensen and prof.dr. Helianthe Kort is much appreciated and acknowledged as well. Finally, the co-operation of companies in the work presented assured that the research topics also aligned with issues of concern in practise.